Huawei TaiShan 200 Product White Paper page 26

Hide thumbs Also See for TaiShan 200:
Table of Contents

Advertisement

TaiShan 200 Server
White Paper (Model 2180)
Categor
y
Altitude
Corrosiv
e
gaseous
contami
nant
Particle
contami
nant
Acoustic
noise
Issue 02 (2020-06-22)
Specifications
3050 m (10000 ft.)
NOTE
ASHRAE 2015 compliant:
● ASHRAE Class A1 and A2 compliant: For altitudes above 900 m (2952.72
ft.), the highest operating temperature decreases by 1°C (1.8°F) for every
increase of 300 m (984.24 ft.) in altitude.
● ASHRAE Class A3 compliant: For altitudes above 900 m (2952.72 ft.), the
highest operating temperature decreases by 1°C (1.8°F) for every increase
of 175 m (574.15 ft.) in altitude.
● ASHRAE Class A4 compliant: For altitudes above 900 m (2952.72 ft.), the
highest operating temperature decreases by 1°C (1.8°F) for every increase
of 125 m (410.10 ft.) in altitude.
Maximum corrosion product thickness growth rate:
● Copper corrosion rate test: 300 Å/month (meeting level G1
requirements of the ANSI/ISA-71.04-2013 standard on gaseous
corrosion)
● Silver corrosion rate test: 200 Å/month
● The equipment room environment meets the requirements of ISO
14664-1 Class 8.
● There is no explosive, conductive, magnetic, or corrosive dust in
the equipment room.
NOTE
It is recommended that the particulate pollutants in the equipment room be
monitored by a professional organization.
The declared A-weighted sound power levels (LWAd) and declared
average bystander position A-weighted sound pressure levels (LpAm)
listed are measured at 23°C (73.4°F) in accordance with ISO 7779
(ECMA 74) and declared in accordance with ISO 9296 (ECMA 109).
● Idle:
– LWAd: 6.08 Bels
– LpAm: 45.2 dBA
● Operating:
– LWAd: 7.0 Bels
– LpAm: 53 dBA
NOTE
Actual sound levels generated during operation vary depending on server
configuration, load, and ambient temperature.
Copyright © Huawei Technologies Co., Ltd.
5 Product Specifications
23

Advertisement

Table of Contents
loading

This manual is also suitable for:

2180

Table of Contents