Huawei SUN2000 Series User Manual page 57

Hide thumbs Also See for SUN2000 Series:
Table of Contents

Advertisement

SUN2000-(29.9KTL, 33KTL-A, 36KTL, 42KTL)
User Manual
Context
Table 5-3 DC terminal selection requirements
Number of Inputs
1
2
3
4
5
6
7
Issue 11 (2019-06-08)
Ensure that the PV module output is well insulated to ground. If the SUN2000 directly
connects to the power grid with the neutral wire connected to the PE cable (for example, a
low-voltage power grid or a power grid with the neutral wire grounded), do not ground the
positive and negative terminals of PV strings. The device may be damaged if you do not
follow the instruction. This damage is not covered under any warranty or service
agreement.
During the installation of PV strings and SUN2000, the positive or negative terminals of
PV strings may be grounded if power cables are not properly installed or routed. In this
case, an AC or DC short circuit may occur and damage the SUN2000. The caused
equipment damage is beyond the warranty scope.
DC terminal selection
Figure 5-15
shows the DC terminals at the bottom of the SUN2000.
the requirements for DC terminal selection.
The SUN2000 provides two DC switches, namely, DC SWITCH 1 and DC SWITCH 2. DC SWITCH 1
controls the first to the fourth routes of DC input terminals, while DC SWITCH 2 controls the fifth to
the eighth routes of DC input terminals.
Figure 5-15 DC terminals
SUN2000
Connects to any route.
Connects to sets 1 and 5.
Connects to sets 1, 3, and 5.
Connects to sets 1, 3, 5, and 7.
Connects to sets 1, 2, 3, 5, and 7.
Connects to sets 1, 2, 3, 5, 6, and 7.
Connects to sets 1, 2, 3, 4, 5, 6, and 7.
Copyright © Huawei Technologies Co., Ltd.
5 Connecting Cables
Table 5-3
describes
50

Advertisement

Table of Contents
loading