SUN2000-(29.9KTL, 33KTL-A, 36KTL, 42KTL)
User Manual
Item
Rated output
voltage
(phase/line
voltage)
Adapted grid
frequency
Maximum
output current
Power factor
Maximum total
harmonic
distortion (rated
power)
Note a: The maximum active power is determined by PQ mode, which can be set on the
SUN2000 app, SmartLogger, or NetEco. If PQ mode 1 is selected, the maximum active
power equals the maximum apparent power. If PQ mode 2 is selected, the maximum active
power equals the rated active power.
Note b: The rated output voltage depends on Grid code, which can be set on the SUN2000
app, SmartLogger, or NMS.
Note c: Choose whether to connect the neutral wire to the SUN2000-29.9KTL,
SUN2000-33KTL-A and SUN2000-36KTL based on the application scenario. When they
are used in the scenarios without the neutral wire, set Output mode to Three-phase,
three-wire. When they are used in the scenarios with the neutral wire, set Output mode to
Three-phase, four-wire.
When the Grid code for the SUN2000-36KTL is set to Mexico-MV480, and the
SUN2000-36KTL is used for power generation in 440 V AC grid connection, you need to
adjust the level-1 and level-2 undervoltage protection threshold to 384 V. The proper AC
output voltage is within the range of 384–576 V.
Protection
Item
Input DC
switch
Anti-islanding
protection
Issue 11 (2019-06-08)
SUN2000-29.9
KTL
230 V/400 V,
b
c
3W+(N)
+PE
50 Hz/60 Hz
43.2 A (400 V)
0.8 leading... 0.8 lagging
< 3%
SUN2000-29.9
KTL
Supported
Supported
Copyright © Huawei Technologies Co., Ltd.
SUN2000-33K
SUN2000-36K
TL-A
TL
230 V/400 V,
220 V/380 V,
c
3W+(N)
+PE
230 V/400 V,
3W+(N)
277 V/480 V,
3W+PE
48 A (400 V)
60.8 A (380
V)/57.8 A (400
V)/48.2 A (480
V)
SUN2000-33K
SUN2000-36K
TL-A
TL
10 Technical Specifications
SUN2000-42K
TL
277 V/480 V,
3W+PE
c
+PE;
56.6 A (480 V)
SUN2000-42K
TL
97