Delta (Del); Controllable Double Point (Dpc) - ABB COM600 3.4 User Manual

Station automation, iec 60870-5-101 master (opc)
Hide thumbs Also See for COM600 3.4:
Table of Contents

Advertisement

1MRS756703
3.4.5.7.
3.4.5.8.
Station Automation COM600 3.4
IEC 60870-5-101 Master (OPC) User's Manual

Delta (DEL)

Table 3.4.5.7-1 Configurable DEL properties for OPC client
Property/ Para-
Value or Value range/ Default
meter
Basic
Common Data
DEL
Class
Sub-Type
Sub Type
DEL Full
DEL Simple
Default: DEL Simple
Addresses
Phase AB Address
0...16777215
Default: 0
Phase BC Address
0...16777215
Default: 0
Phase CA Address
0...16777215
Default: 0
Scale and Unit
Phase Multiplier
Default: Deka
Phase Scale
Lookup Table Scale
Stepwise Linear Scale
Default: None
Phase Unit
Default: Dimensionless
Limit Value Super-
vision
Max
20000
Min
0

Controllable double point (DPC)

Table 3.4.5.8-1 Configurable DPC properties
Property/ Para-
Value or Value range/ Default
meter
Basic
Description
Common data class according to IEC
61850.
Sub Type description.
IEC Address for phase AB (0 = Not in
use).
IEC Address for phase BC (0 = Not in
use).
IEC Address for phase CA (0 = Not in
use).
Multiplier for phase.
Scale for phase.
Unit for phase.
Maximum value for measurement.
Minimum value for measurement.