System Settings (Continued)
142
E-
6
Tracking completed message will appear.
Select Zone initialization mode you want and click [OK].
Not initialize: No zone information initialization will be
made.
Initialize individually: Initialize zone information as
Initialize by group: Initialize zone information as group
mode.
Note
If tracking is executed successfully while IM is set
as communication mode for each channel, virtual
centralized controller will be assigned to each channel.
If there is n searched outdoor units, centralized
controller and SIM/PIM, it is regarded as DVM tracking
failure.
If there are devices which have same address, first
searched device will be registered only.
The number of centralized controller doesn't contain
the number of virtual centralized controller that is used
in NEW communication.
Total number of indoor units includes general indoor
units, ERV, AHU, MINI AHU, Fresh ducts and ERV PLUS.
If you execute tracking, system setting will be initialized.
If tracking result does not match with actual installation
information, there can be critical error in additional
functions such as power distribution.
Make sure that tracking information matches to actual
installation information after tracking.
individual mode.