Samsung BACnet MIM-B17N User Manual page 139

Data management server2 for air conditioner
Hide thumbs Also See for BACnet MIM-B17N:
Table of Contents

Advertisement

System Settings (Continued)
Tracking
What is tracking?
Tracking is an operation that finds devices which are connected to DMS2.
Through tracking operation, devices which are connected to DMS2 can recognize if they are
connecting to DMS2.
To supervise and control system air conditioner using DMS2, tracking should be done first.
Things you can do through tracking
Checking the number of devices installed, setting communication mode by channel, DVM
tracking, Renaming is possible through tracking.
Execute tracking
(1) Connect DVM device
- Connect the device to COM1~COM5.
(2) Set communication mode by channel.
- Set proper communication mode which fits to the devices connected in step (1).
- Be careful that if communication mode is not properly set, the device will not be
found through tracking.
(3) Execute tracking - Execute DVM tracking.
- DVM tracking is an operation that finds system air conditioner devices such as indoor/
outdoor unit, watt-hour meter.
(4) Name setting for each device.
- Name setting for each device is a function that sets the name of connected devices.
Set the name which shows installation location of the device.
Communication mode setting by channel
Roles
- It records what devices are connected to COM1~ COM5 of DMS2.
- Through tracking, DMS2 searches proper devices which fits to user's setting.
- Select proper communication mode which fits to connected device.
What is communication mode?
- Outdoor unit, OnOff controller, SIM, PIM can be connected to DMS2.
- Following is the list of devices that can be communicated through each communication
mode.
NEW mode: OnOff controller and outdoor units which supports new
communication mode.
IM mode: SIM/PIM which only supports conventional communication mode.