(Optional) Connecting T/H Sensors Outside Cabinets
6.2
The T/H sensors outside the cabinet are used to detect the long-distance temperature and
humidity. They can be flexibly installed based on the onsite situation. It is recommended that
the sensors be deployed near heat sources, or near places that lack cooling air. Place the T/H
sensors outside the cabinet near the cabinet and do not directly face them to the air exhaust
vent of the equipment.
1. Connect the IN port on the first T/H sensor outside the cabinet to the RS485/12V port on the
main control board.
2. Connect the OUT port on the T/H sensor outside the cabinet to the IN port on the next T/H
sensor outside the cabinet in series.
3. Set the DIP switches on the T/H sensors.
Name
Air return 2 T/H sensor
Outdoor intake air 1 temp/humid
Outdoor intake air 3 temp/humid
Cold aisle 1 temp/humid
Cold aisle 2 temp/humid
Cold aisle 3 temp/humid
Cold aisle 4 temp/humid
Cold aisle 5 temp/humid
Cold aisle 6 temp/humid
Hot aisle 1 temp/humid
Hot aisle 2 temp/humid
Hot aisle 3 temp/humid
Hot aisle 4 temp/humid
Hot aisle 5 temp/humid
Hot aisle 6 temp/humid
Each smart cooling product supports a
maximum of twelve T/H sensors outside the
cabinet, including a maximum of six cold aisle
T/H sensors and six hot aisle T/H sensors.
(1) RS485/12 V port on the main
control board
(2) Connecting to a T/H sensor
outside the cabinet
Address
1
2
1
ON
OFF
31
ON
ON
32
OFF
OFF
11
ON
ON
12
OFF
OFF
13
ON
OFF
14
OFF
ON
15
ON
ON
16
OFF
OFF
21
ON
OFF
22
OFF
ON
23
ON
ON
OFF
OFF
24
ON
OFF
25
26
OFF
ON
12
DIP Switch ID
3
4
5
OFF
OFF
OFF
ON
ON
ON
OFF
OFF
OFF
OFF
ON
OFF
ON
ON
OFF
ON
ON
OFF
ON
ON
OFF
ON
ON
OFF
OFF
OFF
ON
ON
OFF
ON
ON
OFF
ON
ON
OFF
ON
OFF
ON
ON
OFF
ON
ON
OFF
ON
ON
6
OFF
OFF
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF