Erv (energy recovery ventilator)
Hide thumbs Also See for RHF025EE:
Table of Contents

Advertisement

Product Specifications(cont.)
AN100JSKLKN
Power Source
Ventilation Mode
The Level of the Air Volume
Power Supply(W)
Air Volume(m³/h)
External Static Pressure(Pa)
Cooling
Temperature Exchange
Efficiency(%)
Heating
Cooling
Enthalpy Exchange
Efficiency(%)
Heating
Size(widthxheightxdepth)(mm)
Weight(kg)
Duct Size(mm)
Trial Operation Conditions
2-4
All manuals and user guides at all-guides.com
Heat-Ex Ventilation
Turbo
High
450
280
1000
1000
155
90
70
70
70
70
50
50
70
70
1. Air Volume/ External Static Pressure, Comply with KS Heat Exhaust Ventilation System Standards(KS B6879).
2. Heat Exchange/Temperature Exchange Efficiency, Comply with regulations to pro-
mote high efficiency energy devices,
[Cooling], Indoor(24˚C DB/17˚C WB), Outdoor(35˚C DB/24˚C WB)
[Heating], Indoor(22˚C DB/13.9˚C WB), Outdoor(2˚C DB/0.44˚C WB)
220 - 240 V~, 50 / 60 Hz
By-Pass Ventilation
Low
Turbo
High
155
450
280
690
1000
1000
75
155
90
74
-
74
-
55
-
76
-
1220 × 340 × 1135
67
250
Low
155
690
75
-
-
-
-
-
-
-
-