6. Indoor Units Control from the CCU
6-1-3. MOV minimum pulse adjustment function in cooling operation
Minimum pulse which is set to 60 at the factory is able to adjust (shift).
Minimum pulse under SH control = 60 + XX
EEPROM setting in main outdoor unit
CODE: A9 (for indoor unit capacity 5.6kW or less),
AA (for indoor unit capacity 7.3kW),
AB (for indoor unit capacity over 10.6kW)
1
Setting No
-30
-29
0
50
6-2. RAP valve kit
The RAP valve kit connection might be required on the Type E1 indoor unit.
Mode of
Mode of
indoor unit
outdoor unit
Stop
Cooling
Heating
Fan (only) Cooling
Heating
Cooling
Cooling
Heating
Heating
*RAP valve kit state (ON/OFF) is displayed on "D" in DSBE column when the Checker software is used.
0:OFF
1:ON
In case of special controls, RAP valve kit performs special operation. For detail, refer to Special Controls section.
6-3. Indoor Fan Speed Control
CCU intervenes in fan control of the indoor unit according to the state at the operating mode below.
The priority order of fan control by CCU is higher than that of indoor unit's.
6-3-1. Dry mode
Indoor unit fan operated in the dry mode is controlled from CCU as shown in the below figure.
DTi = (Intake temperature of indoor unit) - (Preset temperature in remote controller)
XX
-30
-29
Interval of "1"
0 ( factory preset mode)
50
Compressor Thermostat
ON/OFF
Stop
-
Operation
-
Stop
-
Operation
-
Stop
-
Operation
-
Stop
-
Operation
-
Stop
-
Operation
OFF
ON
Stop
-
Operation
OFF
ON
DTi
Fan speed set by remote controller
+1
Fan speed is "L" when thermostat ON
Fan speed is "LL" when thermostat OFF
Control Functions - Outdoor Unit
RAP valve kit
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
1 - 20
2WAY SYSTEM