6. Mode Settings
■ Setting mode 2
<Operating procedure>
➀
Press and hold the
simultaneously for 4 seconds or longer.
➁
Press the temperature setting
code. The item codes and setting data are shown in the table below.
➂
Press the timer time
To confirm the changed setting data, press the
(At this time, "SET DATA" display stops blinking and remains lit.)
➃
During this mode, "SET DATA" is displayed, blinking. The display shows the
set outdoor unit address "System XX-YY" (System XX = System address, YY
= Address at outdoor unit sub-bus), item code number (DN value in the table
below), and the setting data (8 digits).
(The setting data is displayed in 8 digits. The display changes between the first 4 digits (Fig.
B
digits (Fig.
). When the first 4 digits are displayed, the top point of the colon is lit.)
➄
To exit setting mode, press the
5
List of Item Codes
DN
Parameter
Outdoor unit capacity
81
(CHECK) button,
button, and
and
and
buttons to change the setting data.
(CHECK) button. Returns to the normal display mode.
A
Display of fi rst 4 digits
1
3
<Refrigerant type> A and B are displayed alternately. (Example
shows 0000 0410 (R410A).)
0 = Disabled, 224 =8HP Type, 280 = 10HP Type, 355 = 12HP Type,
400 = 14HP Type, 450 = 16HP Type, 500 = 18HP Type, 560 = 20HP Type
Outdoor Unit Maintenance Remote Controller
button
buttons to change the item
button.
B
Display of last 4 digits
2
Description
4 - 13