6. Mode Settings
■ Setting mode 2
<Operating procedure>
Press and hold the
simultaneously for 4 seconds or longer.
Press the temperature setting
code. The item codes and setting data are shown in the table below.
Press the timer time
To confirm the changed setting data, press the
(At this time, "SET DATA" display stops blinking and remains lit.)
During this mode, "SET DATA" is displayed, blinking. The display shows the
set outdoor unit address "System XX-YY" (System XX = System address, YY
= Address at outdoor unit sub-bus), item code number (DN value in the table
below), and the setting data (8 digits).
(The setting data is displayed in 8 digits. The display changes between the first 4 digits (Fig.
B
digits (Fig.
). When the first 4 digits are displayed, the top point of the colon is lit.)
To exit setting mode, press the
5
List of Item Codes
DN
Parameter
Outdoor unit capacity
81
(CHECK) button,
button, and
and
and
buttons to change the setting data.
(CHECK) button. Returns to the normal display mode.
A
Display of fi rst 4 digits
1
3
<Refrigerant type> A and B are displayed alternately. (Example
shows 0000 0410 (R410A).)
0 = Disabled, 224 =8HP Type, 280 = 10HP Type, 355 = 12HP Type,
400 = 14HP Type, 450 = 16HP Type, 500 = 18HP Type, 560 = 20HP Type
Outdoor Unit Maintenance Remote Controller
button
buttons to change the item
button.
B
Display of last 4 digits
2
Description
4 - 13
2WAY SYSTEM