* Message configuration
* Message 1 (Configuration #500 to #505, Data #100 to #103)
* Tx Message
* PGN 45568 (HB200), destination 128 (H80)
* event oriented transmission type (ttype K1 >> on data change)
* message priority (0 to 7, 6 default, 0 highest)
* interval for time triggered messages (unused) set K100 = 1 sec.
* message data length count = 8 bytes
*
* Message 2 (Configuration #506 to #511, Data #104 to #107)
* Rx Message
* PGN 45312 (HB100), destination 127 (H7F) this node
* receive message type
* acceptance filter HFF >> any source address OK
* message data length count = 8 bytes
* ################################################################
M0
Online/
Module
Offline
Init.
State
90
M7
11.3 J1939 Communication Example Programs
DTOP
TOP
TOP
TOP
TOP
DTOP
TOP
TOP
TOP
TOP
To the next page
11 Example Program
* <Set 18 bit PGN
D0
K500
H0B280
SFB
address
* <Set ttype K1 (event trigger)
D0
K502
K1
SFB
address
* <Set message priority
D0
K503
K6
SFB
address
* <Interval (unused) 1s
D0
K504
K100
SFB
address
* <DLC = 8 bytes
D0
K505
K8
SFB
address
* <Set 18 bit PGN
D0
K506
H0B17F
SFB
address
* <Set ttype "receive"
D0
K508
K-1
SFB
address
* <From any source address
D0
K509
H0FF
SFB
address
* <Unused for Rx message
D0
K510
K0
SFB
address
* <DLC = 8 bytes
D0
K511
K8
SFB
address
>
K1
>
K1
>
K1
>
K1
>
K1
>
K1
>
K1
>
K1
>
K1
>
K1

Advertisement