Fault Finding - Mitsubishi Electric k-con KSGD-01WS-B Installation And Operation Manual

Refrigerant leak detector
Table of Contents

Advertisement

R
Pre-alarm level 2
Once the
confirmation of the relay operation is required there is no necessity to continue through the
remaining steps
If the detector remains in the
detector will enter the
Operating State
Dual Relay version
Connection
terminal states
Low Level Alarm;
3 & 4
Reading> ~1000ppm
OPEN
For > 30 minutes
4. If test gas application is continued the detector will eventually enter the High Level Alarm
state.
Operating State
Dual Relay version
Connection
terminal states
High Level Alarm
3 & 4
Reading> ~4000ppm
OPEN
For > 30 seconds
5. Turn off the gas regulator valve and allow clean air to circulate over the sensor and the gas
to dissipate. After removing the gas the sensor should recover and return to
Operation.
It may be necessary to ventilate the room with fresh air for the sensor to recover. The time
for the detector to recover will depend upon the concentration of gas detected by the
sensor and the time period but is typically less than 5 minutes. It is recommended that the
sensor is not subjected to test gas for a prolonged period (>3 minutes) as recovery may
become significantly longer.
Please ensure the regulator is switched off after use and the bottle is stored in a ventilated
!
space.
See section 3.1 for supplementary information of Gv voltages at different operational states.
The detectors relays are normally energized, so the operation can also be tested by isolating
power to the detector.

5. Fault finding

Problem
LED Not illuminated
LED Flashing
RED>AMBER
with interval buzzer
fault
LED Flashing
RED
Refrigerant leak
LED Flashing
RED>AMBER
with buzzer puling (2Hz)
LED Flashing
RED>AMBER
with buzzer puling (4Hz)
DO NOT swap the sensor between KSGD units. Each sensor is matched to the PCB and
swapping sensors will directly affect the performance of the product.
KSGD-01WS-B
state is reached, the operation of the detector is proven and unless
skip to step 5.
Pre-alarm level 2
Low Alarm Level
condition.
Single Relay version
Connection
terminal states
5 & 6
3 & 4
CLOSED
OPEN
Single Relay version
Connection
terminal states
5 & 6
3 & 4
CLOSED
OPEN
Sensor
state continuously for 30 minutes the
LED
4 & 5
Flashing
CLOSED
RED>AMBER
(2Hz)
LED
4 & 5
Flashing
RED>AMBER
(4Hz)
CLOSED
Action
Check power supply
Check sensor if fitted and seated correctly in sensor socket
Ventilate room and detector should automatically reset
Potential contaminant, Ventilate room, detector will
automatically reset.
High level contaminant, Ventilate room.
Verify operation of detector.
Buzzer
Gv
Voltage
Pulses
>3.5VDC
2Hz
Buzzer
Gv
Voltage
Pulses
>4.2VDC
4Hz
Normal
Installation and operation manual
KSGD02 Revision: 1.4
Page 14 of 16