Full Operational Test Procedure - Mitsubishi Electric k-con KSGD-01WS-B Installation And Operation Manual

Refrigerant leak detector
Table of Contents

Advertisement

R

4.2 Full Operational test procedure

To verify the correct operation of the
detector, test gas can be used which is
equivalent to the alarm thresholds. Test
kits are available.
1.
Fit pressure regulator on to calibrated gas bottle and check the
cylinder pressure is above 10 bar.
The test gas cylinder should be stored at room temperature or
allowed to stand at room temperature for at least 4 hours prior to
use.
Ensure the detector is powered up for a minimum of 1 hour before
testing.
2. Ensure the detector is in the
before conducting tests gently agitate the bottle for 1 to 2 minutes.
Operating State
Dual Relay version
Connection
terminal states
Normal operation
3 & 4
CLOSED
3.
Place the plastic tube directly over the
perforation on the cover plate and turn the
regulator valve fully anticlockwise to release the
test gas. Apply test gas onto the detector.
As the measured gas level starts to
increase, the detector will enter the
Alarm
states.
Operating State
Dual Relay version
Connection
terminal states
Pre-alarm Level 1;
3 & 4
Reading> ~500ppm
CLOSED
For > 2 seconds
Pre-alarm Level 2;
3 & 4
Reading> ~1000ppm
CLOSED
For > 2 seconds
KSGD-01WS-B
Fig 4.3
Calibration test kit
Normal operation
Single Relay version
Connection
terminal states
5 & 6
3 & 4
4 & 5
OPEN
CLOSED
OPEN
Pre-
Single Relay version
Connection
terminal states
5 & 6
3 & 4
4 & 5
OPEN
CLOSED
OPEN
5 & 6
3 & 4
4 & 5
OPEN
CLOSED
OPEN
Fig 4.4
state before commencing with tests. Just
LED
Buzzer
Constant
GREEN
OFF
Fig 4.5
Applying gas to the detector
LED
Buzzer
Flashing
OFF
GREEN>OFF (2Hz)
Flashing
OFF
RED>OFF (2Hz)
Gas bottle with regulator fitted
Gv
Voltage
0.4>1VDC
Gv
Voltage
>2.5VDC
>3.5VDC
Installation and operation manual
KSGD02 Revision: 1.4
Page 13 of 16