Pulse Output Frequency
Program Terminal Analog Output Terminals
This parameter scales the FP output terminal by setting the
pulses-per-second output signal of the FP terminal.
This parameter is used in conjunction with F676.
Constant at the Time of Filtering
Program Terminal Analog Output Terminals
This parameter is used to select the degree of filtering to be
applied to the AM, FM, and FP output terminals.
The output reading provided by the monitored terminal is filtered
via a rolling average. The sample time of the average is selected
at this parameter.
A longer average time results in a more stable output signal.
FM Voltage/Current Output Switching
Program Terminal Analog Output Terminals
This parameter is used to select the type of output signal pro-
vided at the FM terminal (i.e., voltage or current).
The output voltage and current range is 0 – 10 VDC and 0 – 20
mA, respectively.
See
F005
for additional information on this parameter.
Settings:
0 — 0 – 10 V
1 — 0 – 20 mA
FM Output Gradient Characteristic
Program Terminal Analog Output Terminals
This parameter sets the output response polarity of the FM out-
put terminal. The FM output terminal response may be set to
respond inversely (-) or directly (+) to the input signal.
See
F005
for additional information on this parameter.
Settings:
0 — Minus (Negative Gradient)
1 — Plus (Positive Gradient)
https://www.toshiba.com/tic/
F677
Direct Access Parameter Information
Q9 Plus ASD Install/Op Manual
F683
Direct Access Number —
Parameter Type — Numerical
Factory Default — 3.84
Changeable During Run — Yes
Minimum — 1.00
Maximum — 43.20
Units — Pulses/Second
Direct Access Number —
Parameter Type — Numerical
Factory Default — 64
Changeable During Run — Yes
Minimum — 4
Maximum — 100
Units — mS
Direct Access Number —
Parameter Type — Selection List
Factory Default — 0–10V
Changeable During Run — No
Direct Access Number —
Parameter Type — Selection List
Factory Default — Plus
Changeable During Run — Yes
F677
F678
F681
F682
201