Toshiba Q9+ Installation & Operation Manual page 204

Adjustable speed drives
Table of Contents

Advertisement

PTC 2 Thermal Selection
Program Special  Special Parameters
This parameter Enables/Disables the optional external thermal
detection circuit of the Expansion IO Card Option 2. A thermistor
is connected from TH1+ to TH1- of TB4 on the Expansion IO
Card Option 2.
Should the thermistor resistance reading fall below 50W because
of an over-temperature condition or exceed 3000W because of
an open circuit, an External Thermal Fault (OH2) will be incurred.
Note: While this parameter is Enabled, the system cannot be
restarted until the thermistor value recovers to the level of
1.8 k  from an over-temperature condition. An Auto-
Restart will not be initiated subsequent to an External
Thermal Trip (OH2). A manual restart will be required in the
event of an OH2 trip.
Settings:
0 — Disabled
1 — Detect Disconnect
Braking Resistance Overload Time (not used)
Program Protection Dynamic Braking
This parameter sets the time that the braking resistor is allowed
to sustain an overload condition before a trip is incurred.
This feature is useful for applications that have a fluctuating load
or for loads that require a long deceleration time.
Step-Out Detection Current Level (for PM motors)
Program Motor PM Motor
This parameter is used with synchronous motor applications only.
Contact the TIC Customer Support Center for information on this
parameter.
Step-Out Detection Current Time (for PM motors)
Program Motor PM Motor
This parameter is used with synchronous motor applications only.
Contact the TIC Customer Support Center for information on this
parameter.
192
F638
Direct Access Parameter Information
Q9 Plus ASD Install/Op Manual
F643
Direct Access Number —
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — No
Direct Access Number —
Parameter Type — Numerical
Factory Default — 5.0
Changeable During Run — No
Minimum — 0.1
Maximum — 600.0
Units — Seconds
Direct Access Number —
Parameter Type — Numerical
Factory Default — 100
Changeable During Run — No
Minimum — 10
Maximum — 150
Units — %
Direct Access Number —
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — No
Minimum — 0.0
Maximum — 25.0
Units — Seconds