Page 34 of 105
The following figure shows the AC input switchgear of the HYC_300:
Figure 20: AC input switchgear of the HYC_300
The following table describes the single components highlighted in the figure above:
Identifier
-BE5
-FA1
-FB1
-FB2
-FC1
-QA1, -QA2,
-QA3, -QA4
-QB1
-TB1
-XD1
-XD2
Table 12: AC input switchgear components for hypercharger HYC_300
Remark
All rights reserved. The reproduction of this document, also partially, is allowed only with authorization by alpitronic Srl
Description
AC meter (MID compliant)
Lightning protection and EMI filter device
10 A circuit breaker with fault current monitoring for internal power supply and
service socket
32 A circuit breaker with fault current monitoring (optional, only when AC
charging socket is present)
Input filter circuit
125 A circuit breaker / 3P
500 A main switch / 4P
Auxiliary 24 V power supply
Mains input busbars
Power socket 230 Vac for service
If a residual current device (RCD) is installed, a type B is recommended.
hypercharger - Operation Instructions and Installation Guide
Hardware
Version 2-2
2 Product description