Relay output
Repeatability
*For an integral cable with a length of more than 1.5m a capacitance of 0.3 nF/m shall be
added
For FM/CSA, see FM/CSA connection drawing (Page 32).
Note
A wet location is a location where water or other conductive liquid may be present and is
likely to increase the risk of electric shock.
6.3

Environmental

ambient tem-
perature
ingress protec-
tion
installation category
pollution degree
Pointek CLS100
Compact Operating Instructions, 05/2021, A5E32146158-AB
Integral cable version or enclo-
sure version with stainless steel
process connection
2 mm (0.08")
Integral cable version and Enclo-
sure version with stainless steel
process connection:
Enclosure version with PPS pro-
cess connection:
With ATEX approval:
Enclosure version
Integral cable version
Enclosure version (fully synthetic)
max. switching
60 V DC or 30 V AC;
voltage
limited to 30 V DC/16
V AC in wet locations
max. switching
1 A
current
max. switching
60 W
power
2 mm (0.08")
-30 to +85 °C (-22 to +185 °F)
-20 to +85 °C (-4 to +185 °F) with option FFKM
seal O-ring
-10 to +85 °C (+14 to +185 °F)
Depending on Surface Temperature and Tem-
perature Class, details see Notes for use in
hazardous locations (Page 30).
Type 4 / IP68
Type 4 / IP65
I
4
Technical data
6.3 Environmental
25