Technical Data; Power - Siemens Pointek CLS100 Operating Instructions Manual

Point level switches
Hide thumbs Also See for Pointek CLS100:
Table of Contents

Advertisement

Technical data

6.1

Power

Power supply
Standard
Intrinsically safe
*For an integral cable with a length of more than 1.5m a capacitance of 0.3 nF/ m shall be
added
For more information, see FM/CSA connection drawing (Page 32).
Pointek CLS100
Compact Operating Instructions, 05/2021, A5E32146158-AB
Fully synthetic process
connection, enclosure
version
12-33 V DC
not applicable
Stainless steel process connection, integral
cable or enclosure version
12-33 V DC
10-30 V DC (intrinsically safe barrier required)
For ATEX: U
=30 V I
= 120 mA P
i
i
C
= 2.1 nF* L
= 1.3 mH
i
i
For INMETRO: U
= 30 V I
= 200 mA P
i
i
C
= 2 nF* L
= 1 mH
i
i
6
= 0.8 W
i
= 1.5 W
i
23

Advertisement

Table of Contents
loading

Table of Contents