Installing T/H Sensors
4.3
Installing Remote T/H Sensors for the Smart Cooling Product
1. Unpack the two T/H sensors, and attach one to the 33 U position on the right post of
the front door and the other to the 10 U position on the right post of the rear door of
the cabinet.
2. Set the DIP switch address of the T/H sensor on the front door to 2 and that of the
T/H sensor on the rear door to 1.
3. Insert the pre-routed cable into the port on the T/H sensor on the front door.
Installing T/H Sensors for the Cabinet
1. Unpack the two T/H sensors and attach them to the cabinet posts.
For the 02116410 cabinet, a T/H sensor is installed on the right post of the 39–41 U
position on the front door of the cabinet.
For the 02116411 or 02116412 cabinet, two T/H sensors are installed on the right post
of the 39 U position on the front door and 37 U position on the rear door of the cabinet.
2. Set the DIP switches on the T/H sensors.
For the 02116410 cabinet, set the DIP switch address of the T/H sensor on the front door
to 2.
For the 02116411 or 02116412 cabinet, set the DIP switch address of the T/H sensor on
the front door to 2 and that of the T/H sensor on the rear door to 1.
3.
Insert the pre-routed cable into the port on the T/H sensor on the front door.
The installation positions of the T/H sensors can be adjusted as required.
The default device address is 1.
Installing an Electrode Water Sensor
4.4
12
1. Place the water sensor on the floor under the cabinet.
2. Use an electrician's knife to cut a cross in the rubber plug for the cable hole at the bottom
of the cabinet.
3. Route the water sensor cable through the cable hole at the bottom of the cabinet, and
connect the cable to the water sensor cable connected to the ECC.