14.4. Changing blower external static pressure
The air handler is equipped with an adjustable static pressure setting. The available settings are shown in
the table below.
Model
Available ESP [in. WG]
SVZ-KP12
SVZ-KP18
SVZ-KP24
0.30
0.50
0.80
SVZ-KP30
SVZ-KP36
The air handler will be set to 0.50 ESP from the factory.
The air handler's static pressure can be changed through the mode/function settings in the controller.
Please refer to the installation manual for the controller on how to change this option. Depending on the
controller used, the mode/function will be either 08 for mode (PAR-31 & Simple MA) or 108 for function
(MHK1).
Vertical, Horizontal Left, Horizontal Right External Static Pressure Setting
External Static Pressure
Setting No. of Mode/Function 08/108
0.3 in. WG [75Pa]
0.5 in. WG [125Pa]
(Factory Setting)
0.8 in. WG [200Pa]
Specifications are subject to change without notice.
SVZ-KP12,18, 24, 30, 36NA
Setting No. of Mode/Function 10/110 (Factory Setting)
1
2
3
45
1
1
1
© 2020 Mitsubishi Electric US, Inc.