In the internal logbook, metrologically relevant events (errors, states, actions) are
stored in chronological order with their time of occurrence. The acquired events are
predefined. Logbook data cannot be deleted.
Each event is stored in a separate 4-level shift register. The overflows are trans-
ferred to a 25-level circulating buffer. This way, at least the last 4 times can be
traced for each event.
In a monthly register, the error states are stored for the current month and the past
18 months (without time stamp).
Serial No.
F0 = air in measuring tube
1
F1 = interruption flow temperature sensor
2
F2 = interruption return temperature sensor
3
F3 = error temperature electronics
4
F5 = short-circuit flow temperature sensor
5
F6 = short-circuit return temperature sensor
6
F8 = sensor error > 8 hours
7
F9 = ASIC error
8
Above max. temperature in the flow measuring section
9
Below min. temperature in the flow measuring section
10
Max. flow rate qs exceeded
11
Soiling prewarning
12
Mains voltage off
13
CRC error occurred
14
Adjustment values parameterized
15
F7-(EEPROM) prewarning
16
Reset made
17
Date/time of day parameterized
18
Yearly set day parameterized
19
Monthly set day parameterized
20
Master reset performed
21
All times deleted
22
Missing time deleted
23
Maxima deleted
24
Readout is performed via the optical interface with the service software.
Ultrasonic heat and cooling energy meters UH50..
Description
CE2N5324en
2013-01-14