System Configuration
Parameter Configuration
Type of application
Utilisation of generator
Limit thresholds
Digital Input
Device Configuration
Modbus parameters
ABB ATS022 Initial Configuration Parameters
Parameter
Password
Rated voltage
Rates frequency
Number of phase LN1
Number of phase LN2
Presence of external voltage
Primary voltage TV
Secondary voltage TV
Protection
Priority Line
Switching
Min voltage threshold
Max voltage threshold
Min frequency threshold
Max frequency threshold
Digital Input DI10-function
Digital Input DI10-type
Digital Input DI8-type
DO7
Modbus Address
Modbus Baud Rate
Modbus Stop Bits
Modbus Parity
mode
Backlighting duration
Language
Default Value
0001
100/57V-115/66V-120/70V-208/120V-220/127V-230/132V-240/138V-
400/230 V
277/160V-347/200V-380/220V-400/230V-415/240V-440/254V-480/277V
50 Hz
3 phases with N
3 phases with N/ 3 phases without N/ 1 phase
3 phases with N
3 phases with N/ 3 phases without N/ 1 phase
Absent
100V/57V-115V/66V-120V/70V-208V/120V-220V/127V-230V/132V-
240V/138V-277V/160V-347V/200V-380V/220V-400V/230V-415V/240V-
690/400V
440V/254V-480V/277V-500V/288V-550V/317V-600V/347V-660V/380V-
690V/400V-910V/525V-950V/550V-1000V/577V-1150V/660V
100V/57V-115V/66V-120V/70V-208V/120V-220V/127V-230V/132V-
400/230 V
240V/138V-277V/160V-347V/200V-380V/220V-400V/230V-415V/240V-
2CBs/3CBs NPL opening only/3CBs NPL opening&closing/3CBs NPL
2CBs
Generator not in use
Line LN1
With inverse procedure
With inverse procedure/Without inverse procedure
-15%
+15%
-1%
+1%
Generator Start
disabled/generator start/logic enabling/remote reset/emergency block
NO
NO
0
1
9600
1
absent
local
0s
Always On, 0..59s, step 1s,1,2,3...30min, step 1min
Chinese
English/Italian/German/French/Spanish/Finnish/Russian/Chinese
Value Range
/
50Hz, 60Hz
Absent/Present
440V/254V-480V/277V
BusTie/3CBs Bus Tie
Generator not in use/Generator in use
Line LN1/Line LN2/No priority Line
-30%–-5%
+5%–+30%
-10%–-1%
+1%–+10%
NO/NC
NO/NC
0–63
1...247
9600/19200/38400bps
0
even, odd, absent
local, remote
Setting
0001
400/230 V
50 Hz
3 phases with N
3 phases with N
Absent
690/400V
400/230 V
2CBs
Generator in use
Line LN1
With inverse procedure
-15%
+15%
-1%
+1%
disabled
NO
NO
0
1
9600
1
absent
local
Always On
English