Changeover Control (Me1 Series) - Panasonic Urban Multi MX1R Series Service Manual

Using r-407c / r-22
Table of Contents

Advertisement

Function
1.11
HR Changeover Control (ME1 Series)
The solenoid valve of the HR box is switched according to the indoor unit operating condition.
Condition
When the solenoid is operable, if the operating condition differs from the solenoid condition, the solenoid is
switched according to the above table.
However, the following conditions take precedence.
∗ 1 : Condition 2 results in heating stop units when no unit in the system is in cooling operation.
∗ 2 : Condition 1 results when a unit connected to the HR box is in heating thermostat ON condition
38
Normal operation
Condition 1
Cooling
Condition 2
Heating
Indoor unit operating condition
1
Cooling
Heating stop ∗1
2
Heating thermostat OFF
Heating thermostat ON
3
Discharge oil return
4
Suction oil return
Defrost
during simultaneous cooling/heating operations.
Oil return, defrost
Oil return, defrost complete
Y3S
Y2S
OFF
ON
ON
OFF
OFF
OFF
ON
ON
Function Urban Multi "MX1, ME1 Series" Using R-22
PACD011001C2
Oil return, defrost
Discharge defrost
Condition 3
Discharge oil return
Suction defrost
Condition 4
Suction oil return
(VF006)
Y1S
ON: Open
OFF: Closed
OFF
∗2
OFF
OFF

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents