Low Noise / Demand Operation (Mx1R Series) - Panasonic Urban Multi MX1R Series Service Manual

Using r-407c / r-22
Table of Contents

Advertisement

PACD011001C2
1.11

Low Noise / Demand Operation (MX1R Series)

BMS interface adaptor for outdoor unit is required for each low noise and demand control zone.
„ By using a separate BMS interface adaptor for outdoor unit and setting the outdoor unit address (setting
„ Outdoor unit address setting (Setting mode 2; see page 283.)
„ BMS interface adaptor for outdoor unit address setting
‹ Decide and set demand address 0 - 31 for each demand and low noise control zone. (See fig. below.)
‹ Set SS1 to "BOTH" (factory set) or "C / H."
Test Operation Urban Multi "MX1R, ME1R Series" Using R-407C
mode 2) for each low noise and demand control zone, demand and low noise operation is carried out in
accordance with contact input received from the adaptor in each zone.
¡
llllll
Demand address
F1 / F2
F1 / F2
F1 / F2
(F1 / F2)
BMS interface
adaptor for
outdoor unit
DS2·DS1
No. 0
¡
¡
lllll
Demand address
F1 / F2
F1 / F2
F1 / F2
F1 / F2
(F1 / F2)
BMS interface
adaptor for
outdoor unit
DS2·DS1
No. 1
Test Operation
¡
¡
llll
l
Demand address
F1 / F2
F1 / F2
F1 / F2
(F1 / F2)
BMS interface
adaptor for
outdoor unit
DS2·DS1
No. 2
(M048)
311