Certification
6.3 EMC and Environmental Type Tests
6.3

EMC and Environmental Type Tests

The RUGGEDCOM MX5000 has passed the following EMC and environmental tests.
IEC 61850-3 EMC Type Tests
IEC 61000-4-2
IEC 61000-4-3
IEC 61000-4-4
IEC 61000-4-5
IEC 61000-4-6
IEC 61000-4-8
IEC 61000-4-29
IEC 61000-4-11
IEC 61000-4-12
IEC 61000-4-16
IEC 61000-4-17
IEC 60255-5
42
Test
ESD
Radiated RFI
Burst (Fast Transient)
Surge
Induced
(Conducted) RFI
Magnetic Field
Voltage Dips
& Interrupts
Voltage Dips
& Interrupts
Damped Oscillatory
Mains Frequency
Voltage
Ripple on DC
Power Supply
Dielectric Strength
Description
Enclosure Contact
Enclosure Air
Enclosure Ports
Signal ports
DC Power ports
AC Power ports
Earth ground ports
Signal ports
DC Power ports
AC Power ports
Signal ports
D.C Power ports
AC Power ports
Earth ground ports
Enclosure Ports
DC Power ports
AC Power ports
AC Power ports
Signal ports
DC Power ports
AC Power ports
Signal ports
DC Power ports
DC Power ports
Signal ports
Test Levels
+/- 8 kV
+/- 15 kV
20 V/m
+/- 4 kV @ 2.5 kHz
+/- 4 kV
+/- 4 kV
+/- 4 kV
+/- 4 kV line-to-earth,
+/- 2 kV line-to-line
+/- 2 kV line-to-earth,
+/- 1 kV line-to-line
+/- 4 kV line-to-earth,
+/- 2 kV line-to-line
10 V
10V
10V
10V
100 A/m
1000 A/m for 1 s
30% for 0.1 s, 60% for
0.1 s, 100% for 0.05 s
30% for 1 period,
60% for 50 periods
100% for 5 periods,
100% for 50 periods
2.5 kV common, 1 kV
differential mode @1 MHz
2.5 kV common, 1 kV
differential mode @1MHz
2.5 kV common, 1 kV
differential mode @1MHz
30 V Continuous,
300 V for 1 s
30 V Continuous,
300 V for 1 s
10%
2 kV (Fail-Safe
Relay output)
RUGGEDCOM MX5000
Installation Manual, 01/2021, C79000-G8976-1059-13
Severity
Levels
4
4
a
Note
a
Note
4
4
4
4
3
4
3
3
3
3
 
5
 
 
 
3
3
3
4
4
3
 

Advertisement