Huawei SUN2000-2KTL-L1 User Manual page 90

Hide thumbs Also See for SUN2000-2KTL-L1:
Table of Contents

Advertisement

SUN2000-(2KTL-6KTL)-L1
User Manual
Alarm
Alarm Name
ID
2032
Grid Failure
2033
Grid
Undervoltage
Issue 04 (2021-04-01)
Alarm
Possible Causes
Severity
Major
Cause ID = 1
● The power grid
experiences an outage.
● The AC circuit is
disconnected or the AC
circuit breaker is OFF.
Major
Cause ID = 1
The grid voltage is below
the lower threshold or the
low voltage duration has
lasted for more than the
value specified by low
voltage ride-through
(LVRT).
Copyright © Huawei Technologies Co., Ltd.
8 System Maintenance
Troubleshooting
1. Check the AC voltage.
2. Check whether the AC
circuit is disconnected or
the AC circuit breaker is
OFF.
1. If the alarm occurs
occasionally, the power
grid may be abnormal
temporarily. The
SUN2000 automatically
recovers after detecting
that the power grid
becomes normal.
2. If the alarm occurs
frequently, check
whether the power grid
voltage is within the
allowed range. If no,
contact the local power
operator. If yes, modify
the grid undervoltage
protection threshold
through the mobile app,
SmartLogger, or network
management system
(NMS) with the consent
of the local power
operator.
3. If the fault persists for a
long time, check the
connection between the
AC switch and the
output power cable.
84