External Communication Connector; Figure 2.18 External Communication Connector (Nec Class2) - Toshiba G8000MM Series Installation And Operation Manual

Hide thumbs Also See for G8000MM Series:
Table of Contents

Advertisement

Terminals 9 to 18 "Spare" contact input (IN5 through IN9)
Terminals 19 to 20 "Remote EPO" contact input
Used to perform a remote UPS Emergency Power Off (EPO).
The load will be dropped.
!
The UPS is equipped with a selectable output contact item.
The above items are the default settings.
Contact Toshiba International Corporation for setup information
NOTE
In all cases, a switch having a protective cover is recommended in
order to reduce the possibility of accidental operation
CAUTION
2.5

External communication connector

This is an RS232C port for "RemotEyeII"* monitoring software.
The layout of connector is shown in Figure 2.18.

FIGURE 2.18 External communication connector (NEC Class2)

D-SUB 9Pin (male)
6
7
8
9
PCB IOAU-04
* Consult Toshiba International Corporation for details on
its capabilities.
32
Pin 1.
Pin 2. RXD
Pin 3. TXD
Pin 4.
1
2
Pin 5. GND
3
4
Pin 6.
5
Pin 7.
Pin 8.
Pin 9.
: Not used
: Receive data
: Transmit data
: Not used
: Signal ground
: Not used
: Not used
: Not used
: Not used
"
RemotEyeII
"