Communication Interfaces; Remote Contacts - Toshiba 5000 Series Installation And Operation Manual

Industrial ups. 3-phase, 480vin - single phase, 120vout
Hide thumbs Also See for 5000 Series:
Table of Contents

Advertisement

10

Communication Interfaces

10.1

Remote Contacts

The remote contacts interface is provided as a set of solid state switching devices. The switches are available through an
I/O Switching Interface board located in the Instrumentation compartment of the I/O Bay on the right side of the UPS. The
following chart shows the pin assignment for each signal.
Specifications
TB1, TB3: SPDT (1NO/1NC)
DC Volt / DC Amp Rating
TB2, TB4: SPDT (1NO/1NC)
DC Volts / DC Amp Rating
Wire Capacity
Torque
TB
Lug
-1
COM
-2
NC
-3
NO
-4
COM
-5
NC
-6
NO
-7
COM
-8
NC
-9
NO
-10
COM
-11
NC
-12
NO
TB1
-13
COM
-14
NC
-15
NO
-16
COM
-17
NC
-18
NO
-19
COM
-20
NC
-21
NO
-22
COM
-23
NC
-24
NO
36
TABLE 10.1: TERMINAL BLOCK SPECIFICATIONS
30 Vdc / 3 A, 125Vac / 3A
24Vdc / 8.3 mA
#18 AWG - #12 AWG
4.4 - 5.3 in.-lb (0.5 - 0.6 N·m)
TABLE 10.2: TERMINAL BLOCK SIGNAL MAP
SIGNAL
5000 Series 3P1 Industrial UPS Installation and Operation Manual – 92973-001
Value
OPERATION
OUT1: LOAD ON BYPASS
OUT2: LOAD ON INVERTER
OUT3: BATTERY OPERATION
OUT4: WARNING OCCURRED
OUT5: BATTERY SHUTDOWN WARNING
OUT6: OVERLOAD
OUT7: BATTERY LOW WARNING
OUT8: FAULT OCCURRED

Advertisement

Table of Contents