3.2.8
Insulation resistance test using megger
• For the inverter, conduct the insulation resistance test on the main circuit only as follows and do not perform the test on
the control circuit.
(Use a 500 VDC megger.)
NOTE
• Before performing the insulation resistance test on the external circuit, disconnect the cables from all terminals of the inverter
so that the test voltage is not applied to the inverter.
• For the continuity test of the control circuit, use a tester for high resistance range and do not use the megger or buzzer.
Power
supply
500 VDC
megger
3.2.9
Withstand voltage test
Do not conduct a withstand voltage test. Deterioration may occur.
Motor
R/L1
U
Inverter
IM
S/L2
V
T/L3
W
3. Precautions for Maintenance and Inspection
3.2 Measurement of main circuit voltages, currents, and powers