5.6.5 Min Ramp-up Time [s]
Variable
SNVT
name:
type:
nciRampUpTime
SNVT_time_sec
This variable configures the ramp-up time and associates it with par. F-07 Accel Time 1.
5.6.6 Min Ramp-down Time [s]
Variable
SNVT
name:
type:
nciRampDownTime
SNVT_time_sec
This variable configures the ramp-down time and compares it with par. F-08 Decel Time 1.
5.6.7 Heartbeat Time [s]
Variable
SNVT
name:
type:
nciSndHrtBt
SNVT_time_sec
This variable configures a heartbeat timer to send the following variables:
nvoDrvCurnt
nvoDrvSpeed
nvoDrvVolt
nvoDrvPwr
Setting the timer to 0.0 disables the timer.
Heartbeat timers have the purpose of sending out heartbeat signals containing specific data, enabling management systems to prove that the node is present
on the network and working correctly. Only bound variables will be transmitted.
Default value:
Min value:
10 s
1 s
Default value:
Min value:
10 s
1 s
Default value:
Min value:
0 s
0 s
AF-600 FP LonWorks
Max value:
3,600 s
Max value:
5
3,600 s
Max value:
6,553.4 s
33