5.2 Network Variable Description
5.2.1 - Drive VSD Profile - Input
Start/Stop
Variable
name:
nviStartStop
5
This variable sends a Start or Stop command to the frequency converter and a reference (0 - 100 %)
NB!
The reference value of nviStartStop will only be valid if both nviRefPcnt and nviRefHz are = 0
Control Word
Variable
name:
nviControlword
The input network variable nviControlWord is a 16-bit word providing additional operational control of the frequency converter.
For more information about the Control word, please refer to the GE Drive Control Profile section.
NB!
Please note in the representation of the Control Word in the LonMaker Browser, the LSB is to the far left.
Reset fault
Variable
name:
nviResetFault
This variable sends a reset command to the frequency converter via bit 7 in the Control Word (0x04BC), see the GE Drive Control Profile section.
18
SNVT
State:
type:
SNVT_switch
0 (False)
1 (True)
1 (True)
1 (True)
0xFF (default)
SNVT
type:
SNVT_state
SNVT
State:
type:
SNVT_switch
0 (False)
1 (True)
0xFF (default)
Value:
Command:
Any
Stop (0x043C)
0
Running 0% (0x047C)
1-200
Running 0.5 to 100.0%
201-255
Running100%
Any
AUTO (invalid, no action)
State:
Boolean 1 bit x 16
Value:
Command:
Any
No reset
Any
Reset (0x04B)
Any
AUTO (invalid, no action)
AF-600 FP LonWorks