Huawei NetCol8000-E220 Series Quick Manual page 5

Modular indirect evaporative cooling system
Hide thumbs Also See for NetCol8000-E220 Series:
Table of Contents

Advertisement

2. Connect the steel hoisting ropes, and hoist the device onto the concrete platforms.
3. Use M12 screws to secure the air duct to the floor or concrete platform.
Indoor scenario
Outdoor scenario
4. Secure the equipment to the concrete platform using four right angle brackets.
5

Advertisement

Table of Contents
loading

This manual is also suitable for:

Netcol8000-e220dm0aaNetcol8000-e220dm0baNetcol8000-e220

Table of Contents