Post-Installation Check - Huawei NetCol8000-E220 Series Quick Manual

Modular indirect evaporative cooling system
Hide thumbs Also See for NetCol8000-E220 Series:
Table of Contents

Advertisement

(Optional) Connecting T/H Sensors Outside Cabinets
6.2
The following figure shows the position of the
return air temperature and humidity sensor in
the smart cooling product. The cable passes
through the cable hole to remote T/H sensor.
Set the sensor positions based on their location
and the following table.
1. Connect the T/H sensor cables.
After the addresses are set, power on the
device. On the display's home screen, choose
Settings > System Settings > T/H Sensor, and
set the sensors in the aisles corresponding to
the addresses to Enable. Otherwise, the
sensors will not work.
2. Set the DIP switches on the T/H sensors.
Name
Cold aisle 1 temp/humid
Cold aisle 2 temp/humid
Cold aisle 3 temp/humid
Cold aisle 4 temp/humid
Cold aisle 5 temp/humid
Hot aisle 1 temp/humid
Hot aisle 2 temp/humid
Hot aisle 3 temp/humid
Hot aisle 4 temp/humid
Hot aisle 5 temp/humid
(Optional) Connecting Teamwork Network Cable and Monitoring Cable
6.3
(1) FE_1 (input and output port on the FE ring network)
(2) CAN_IN (input port of the teamwork CAN/northbound
RS485 port)
(3) RS485/12 V (T/H module port)
(4) USB (USB port)
(5) DP (connected to the display port)
(6) COM/FE (northbound RS485 port)
8

Post-Installation Check

(7) CAN_OUT (output port of the teamwork CAN/northbound
RS485 port)
(8) FE_2 (input and output port on the FE ring network)
(9) SW (for restoring factory settings)
(10) Alarm indicator
(11) Run indicator
Address
1
11
ON
12
OFF
13
ON
14
OFF
15
ON
21
ON
22
OFF
23
ON
OFF
24
ON
25
13
DIP Switch ID
2
3
ON
OFF
ON
OFF
ON
ON
OFF
ON
ON
ON
ON
ON
ON
ON
ON
OFF
ON
OFF
ON
ON
OFF
ON
ON
OFF
OFF
OFF
ON
OFF
OFF
ON
4
5
6
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF

Advertisement

Table of Contents
loading

This manual is also suitable for:

Netcol8000-e220dm0aaNetcol8000-e220dm0baNetcol8000-e220

Table of Contents