Huawei NetCol8000-E220 Series Quick Manual page 14

Modular indirect evaporative cooling system
Hide thumbs Also See for NetCol8000-E220 Series:
Table of Contents

Advertisement

CAN teamwork networking (CAN Protocol)
1. Prepare the 8pin standard network cable, the cable pin sequence requirements are shown below.
2. Connect the CAN_OUT port of each smart cooling product to the CAN_IN port of the following
smart cooling product using a CAN network cable.
RS485 Monitoring Network Cable (Modbus-RTU Protocol)
1. Make the COM network cable by referring to the following figure.
2. Group smart cooling products for monitoring based on performance requirements and connect
the monitoring network cables.
If there is no teamwork control, connect the COM/FE port on each smart cooling product to the
customer's monitoring system.
In CAN networking and no grouping, connect the COM/FE port on the last smart cooling product
to the monitoring device. After powering on the device, set the "RS485 monitoring grouping" of
the last smart cooling product to "Enable". Setting path: Settings > Comm Settings > Modbus
Settings.
Except for pins 4 and 5, the
cable of other pins must be cut
off to prevent interference.