Huawei PDU8000 Quick Manual page 13

Ups modular input power distribution cabinet (single cabinet)
Hide thumbs Also See for PDU8000:
Table of Contents

Advertisement

Ties without sharp burs
Binding cables of different colors
Cable Bending
No.
Cable Bending Rules
1
Cables must not be overly bent as over bending may damage the cable cores.
Unless otherwise stipulated, the bending radius should be ten times more than the cable
2
diameter if the installation space is sufficient.
3
Cables must not be tied where they bend, as shown in the figure.
Cables must be a little longer than the exact cable route length to facilitate plug and
4
unplug, as shown in the figure.
Cables should be neatly and loosely aligned to eliminate abnormal stress on certain cables,
5
as shown in the figure.
No tie at a bend
Ties in the same direction
Cable binding interval
Cable Bundle Diameter
(mm)
< 10
10–30
> 30
Extra length for easy plug and unplug
Neatly and loosely aligned
12
Binding Interval
(mm)
150
200
300