6.2.2
Setting procedure for PROFIsafe
The following section describes settings for FR-E800-SCE PROFIsafe.
Settings for PROFINET
Refer to the FR-E800 Instruction Manual (Communication).
Enabling PROFIsafe
Set "3" in Pr.S002 Safety communication function selection to enable PROFIsafe.
Refer to details of safety parameters
NOTE
• PROFIsafe is not affected by the IP address specification for Ethernet command source selection (Pr.1449 to Pr.1454).
Setting parameters for safety sub-functions
Configure settings for safety sub-functions to be used.
Refer to details of safety parameters
PROFIsafe communication connection settings
1.
Set the PROFIsafe destination address (F_Dest_Add) using the engineering software of the master.
2.
Set the same value as the PROFIsafe destination address (F_Dest_Add) in the safety parameter Pr.S089
PROFIsafe address using FR Configurator2.
Communication error detection settings
Use the engineering software of the master to configure settings for communication error detection.
Parameter
Watchdog time
(F_WD_Time)
40
6. Safety Communication Functions
6.2 PROFIsafe
(page
14).
(page
14).
Description
1500 ms to 10000 ms
A timeout error occurs when the time set in the
parameter elapses.