Monitoring Function - Mitsubishi Electric EcoMonitorPro EMU2-RD3-F Instruction Manual

Energy measuring unit
Table of Contents

Advertisement

Supplementation ----------------------------------------------------------------------------------------------------------------------------------------------------------------
• Measuring parameters to be displayed on the display unit can be selected. For the details, see the instruction manual for each display
unit.
• The measuring conditions of following item vary with the phase wire system.
Item
Total current
Total voltage
Maximum current
Minimum current
Maximum voltage
Minimum voltage

10.2 Monitoring function

The parameters to be monitored are shown in the following table.
Monitoring item
Current demand
upper/lower limit alarm
Voltage upper/lower limit
alarm
Power demand upper/lower
limit alarm
Power factor upper/lower
limit alarm
Supplementation ----------------------------------------------------------------------------------------------------------------------------------------------------------------
• This unit has only a function to monitor the conditions of occurrence of upper/lower limit alarms and the history of upper/lower limit
alarms (date and time of occurrence and values upon occurrence) on the display unit.
• To monitor the current and electric power as instantaneous values, set the demand time limit to 0 second.
• The upper and lower limits can be set only on the display unit. They cannot be set by CC-Link.
• Each value upon occurrence and date and time of occurrence can be checked only on the display unit. They cannot be read by CC-Link.
On CC-Link, only the alarm status can be checked.
Phase wire system
Single-phase 2-wire
Single-phase 3-wire, 3-phase 3-wire
3-phase 4-wire
Single-phase 2-wire
Single-phase 3-wire, 3-phase 3-wire
3-phase 4-wire
Single-phase 3-wire
3-phase 3-wire
3-phase 4-wire
Single-phase 3-wire
3-phase 3-wire
3-phase 4-wire
Single-phase 3-wire
3-phase 3-wire
3-phase 4-wire
Single-phase 3-wire
3-phase 3-wire
3-phase 4-wire
Detail
Value upon
occurrence
Date and time of
occurrence
Value upon
occurrence
Date and time of
occurrence
Value upon
occurrence
Date and time of
occurrence
Value upon
occurrence
Date and time of
occurrence
Measuring condition
Total current = I
R
Total current = (I
+ I
)/2
R
T
Total current = (I
+ I
+ I
R
S
Total voltage = V
R-S
Total voltage = (V
+ V
R-S
T-R
Total voltage = (V
+ V
R-S
S-T
Larger value of I
or I
R
T
Largest value of I
, I
and I
R
S
Largest value of I
, I
, I
R
S
T
Smaller value of I
or I
R
T
Smallest value of I
, I
and I
R
S
Smallest value of I
, I
and I
R
S
Larger value of V
or V
R-S
T-R
Largest value of V
, V
R-S
S-T
Largest value of V
, V
R-S
S-T
Smaller value of V
or V
R-S
Smallest value of V
, V
R-S
S-T
Smallest value of V
, V
R-S
S-T
(18/32)
)/3
T
)/2
+ V
)/3
T-R
T
and I
N
T
T
and V
T-R
and V
T-R
T-R
and V
T-R
and V
T-R