Upper And Lower Limit Settings - Mitsubishi Electric EcoMonitorPro EMU2-RD3-F Instruction Manual

Energy measuring unit
Table of Contents

Advertisement

■ Upper and lower limit settings [Defaults: Upper limit setting = Max. setting Lower limit setting = Min. setting]
The upper and lower limits can be set for each circuit as shown below. The upper and lower limits can be set only on the display unit. They
cannot be set by CC-Link communication.
◆ Current demand upper/lower limit settings
Rated primary current setting
5A to 30A
40A to 300A
400A to 3000A
4000A to 30000A
◆ Voltage upper/lower limit setting
Rated primary voltage setting
110 V to 220 V
440 V to 2200 V
3300 V to 110000 V
◆ Power demand upper/lower limit setting
Full-load power (kW)
Less than 12
12 to less than 120
120 to less than 1200
1200 to less than 12000
12000 to less than 120000
120000 or over
◆ Power factor upper/lower limit setting
Min. upper/lower limit
setting
LEAD 0.50
◆ Alarm delay time [Default: 10 sec]
The setting is applied to all upper/lower limit alarms.
0, 5 sec, 10 sec, 20 sec, 30 sec, 40 sec, 50 sec, 1 to 5 min (in 1-min steps)
Min. upper/lower limit setting
0.00A
0.0A
0A
0A
Min. upper/lower limit setting
0.0 V
0 V
0 V
Min. upper/lower limit
setting
0.000 kW
0.001 kW
0.00 kW
0.01 kW
0.0 kW
0.1 kW
0 kW
1 kW
0 kW
10 kW
0 kW
100 kW
Max. upper/lower limit
Setting step
setting
0.05
LAG 0.50
Setting value
(14/32)
Setting step
Max. upper/lower limit setting
0.01A
Rated primary current setting
0.1A
1A
10A
Setting step
Max. upper/lower limit setting
0.1 V
Rated primary voltage setting
× (15/11)
1 V
10 V
Setting step
Max. upper/lower limit setting
Full-load power