Marine fire damper with atex rated electrical (schischek) actuator

Advertisement

Quick Links

D
IOM
1. Description
 The actionair Marine Fire Damper is tested and approved for
fitting to class A-0 A-15 A-30 A-60 divisions (bulkheads and
decks), when suitably insulated.
A-0 does not require any insulation to the casing.
2. Tests, approvals and certification
 Lloyds Register Approved.
 DNV-GL Approved.
 ABS Approved
 USCG Approved.
 Transport Canada approved.
 MED Marine Equipment Directive Compliant.
 Fire tested to the latest IMO FTP code & in compliance with the
international convention for the safety of life at sea (SOLAS)
 Sira certification (Ex) category 2 equipment
 Corrosion Tested - EN60068-2-52 severity 2 conditions
 Vibration Tested – EN60068-2-6 (5Hz to 350Hz @2g)
3. Health and Safety
 Care must be taken when installing and inspecting dampers,
as they are likely to close without warning due to loss of
electrical power, or a temperature rise in the ductwork. This is
their prime function.
Do not introduce any items, fingers or limbs between the
blades.
 Larger dampers are heavy and must be handled in accordance
with current local regulations and good practice.
 All wiring should be carried out in accordance with the wiring
details provided, to the IEC regulations.
4. General Information
 The actionair Marine Fire Damper is suitable for both vertical
and horizontal applications, with airflow in either direction.
 The dampers tested to IMO fire test procedures Code, Annex 1
Pt 3, are normally open, and fail-safe to the closed position. The
actionair Marine Fire Dampers are supplied with the blades in
the fully interlocked closed position to avoid damage during
transit and installation. It is recommended that the dampers
remain closed until actual date of commissioning. All fire
dampers are life safety products and must be treated with care
during handling, storage and installation.
www.actionair.co.uk
sales@actionair.co.uk
0038/YYYY
YYYY Denotes
the year the
Wheel mark
is affixed to damper
Fire Damper
With ATEX rated
(Schischek) Actuator
 Actionair Marine Fire Dampers are designed for applications in
normal dry filtered air systems and should be subjected to a
planned inspection programme.
5. Installation - see below.
6. Maintenance & Cleaning
 Dampers are supplied in two casing and blade material
options: -
1/ Galvanised Steel casing and 430 Stainless steel blades, only
suitable for installation in dry filtered systems.
2/ 316 Stainless steel casing and blades and drive - more suited
for corrosive conditions, but even this will rapidly corrode and
fail if not properly maintained, when used in air intake systems
at sea. The addition of a mist eliminator is highly recommended,
and access must be provided for maintenance.
7. Testing
Two levels of testing exist.
 Routine testing - Monthly, or in accordance with maintenance
programme, release and reset damper (via control system or
ETR test switch). Check remote indication or visual check of
mechanical pointer as appropriate.
 Visual check at damper - At commissioning and at least once
a year, check damper operation by removing and
re-applying power to actuator. (via ETR test switch).
 Visually check blades for damper closed and open positions.
Prove remote indication if applicable.
8. Routine Maintenance
 Depending upon environmental conditions, each damper will
merit its own cleaning regime. Particularly hostile areas.
 'Frequency of maintenance' should be determined by
collecting historical data from previous visits, and for this
reason, commence maintenance programmes.
 Dampers in 'Dry Filtered Air' require very limited maintenance.
When exposed to fresh air intakes and/or inclement conditions
this may require monthly cleaning and lubrication maintenance
to be performed.
9. Cleaning
 Using light lubricant, clean all exposed surfaces, using a cloth.
Remove all traces of surface staining, as this will deteriorate
further causing deeper material corrosion.
 For 316 stainless steel blades and case, pay specific attention
to the blade rivets where crevice corrosion will cause rapid
failure of blades if not kept in check.
 If damper is stiff to operate lubricate blade ends, open and
close damper successively until the damper moves with ease.
(This may necessitate removal of the actuator and operating
the blades manually by the drive shaft).
 Refit actuator and re-test.
 Clean off excessive lubricant.
A60 Marine
Electrical

Advertisement

loading
Need help?

Need help?

Do you have a question about the Actionair A60 and is the answer not in the manual?

Questions and answers

Summary of Contents for Swegon Actionair A60

  • Page 1 A60 Marine Fire Damper With ATEX rated Electrical (Schischek) Actuator  Actionair Marine Fire Dampers are designed for applications in normal dry filtered air systems and should be subjected to a planned inspection programme. 5. Installation - see below. 6. Maintenance & Cleaning ...
  • Page 2 10. Damper installation Bolt holes provided as standard on the damper flanges (unless otherwise stated) at 150mm maximum centres. Matching hole All installations shall be carried out in accordance with the positions are necessary on mating coaming/duct flanges. relevant Marine/Offshore Authority requirements. Apply approved fire-resistant sealant/gasket to mating flanges The damper should be installed in accordance with Insulation and position damper.
  • Page 3 11. Control Modes (3 positions) (Refer to figure 8) Electrical ATEX (Ex) rated as below Fail-safe is by means of an ExPro-TT which operates at 72 °C, or Two sizes of Control Modes are utilised - 5.10Nm & 15Nm. if power supply is interrupted. Correctly sized Control Modes are designed to fit only to the A manual test button (Refer to figure 7) allows periodic relevant sized damper.
  • Page 4: Test Button

    15. Actuator installation 16. Three position Actuator mounting & dimensional date Actuator mounting brackets riveted to damper casing Schischek 15Nm Schischek 5.10Nm Actuator mounting plate Damper drive shaft Figure 8 Screw Washer Pointer 2 spacers ExPro TT Figure 6 Test button ExPro TT Figure 7 Safety...
  • Page 5 17. Application & wiring --------Important --------- Please fully read the Schischek data sheets provided with every actuator For 5.10 actuators 10Nm & 3 sec/90° must be selected. For 15Nm actuators 3 sec/90° must be selected. Make sure that 1 cycle per minute is not exceeded. www.actionair.co.uk sales@actionair.co.uk...
  • Page 6: Recommended Action

    If necessary, remove Control Mode and operate damper drive shaft with 14mm A/F spanner. Over tightening of M5 x 80mm Loosen screw to 5Nm torque. screw. (3 position only) Swegon Air Management are ISO9001 & ISO 14001 certified LNNN00315 – REV 5 www.actionair.co.uk...