A.2 Requirements for the STS-6000K-H1 Foundation
Dimensions
The technical requirement:
Issue 02 (2020-02-21)
Purpose
Logo
Construct a foundation of the correct dimensions based on the site design drawing. The
preceding figure is for reference only.
Unmarked sizes shall be determined according to onsite conditions.
Reserve pressure relief channels for the ring main unit, and add protective measures to
prevent high temperature gas from burning nearby personnel during pressure relief.
The ladder should not block the low voltage and MV cables in and out. The insulation
ladder is recommended to be put in front of the door when maintenance.
The size of each cement column is recommended to be no less than 6218 mm x 600 mm,
and the container shall be placed in the center of the foundation. Height of the column
shall be determined according to the actual situation on site.
The outline of the smart transformer station is 6058 mm (L) x 2438 mm (W).
Weight of STS-6000K-H1 is no more than 22 t and transformer oil is mineral oil,
noncorrosive. And the volume of transformer oil is about 3850 L (about 3.4 t).
Copyright © Huawei Technologies Co., Ltd.
Paint Model
EPICON ZINC SC B-2 M(ON LINE ZINC)
Intermediate coat: EPICON SC PRIMER GREY
CSC-9107
Top coat: UNYMARINE SC FINISH WHITE
CSC-9205 (RAL-9003)
Red: UNYMARINE SC MARKING RAL-3020
Black: UNYMARINE SC MARKING
RAL-9005