3. Place the battery pack on the guide rails. Secure the battery pack to the rack using M6x16 screws
through the holes in the mounting bracket.
Ensure that the rack is properly grounded
before the operation.
1. Do not move the battery pack by holding its mounting brackets, front panel, or terminal cover.
2. Remove rings, watches, and other metal objects before you move a battery pack.
3. Do not push the guide rails out of the race when putting the battery pack into the rack, as the
front end of the guide rails are not screwed.

Tower-mounting Battery Packs

1. The text uses how to install a battery packs and a 6 kVA UPS as an example.
2. The support base length is adjustable. You can add components to increase the length. A
component (1 U) installed between the support bases is required for a 3 U device.
3. Exert force to disassemble components in the reverse directions of assembling.
4. The minimum distance between two support bases should be 280 mm and the maximum should
not exceed the edge of the device. It is recommended that the distance between the front (rear)
base and the front (rear) side of the device should be about 100 mm.
1. Assemble support bases. When you assemble two support bases, align connecting buckles with
holes and insert the buckles vertically, as shown in the following figure.
2. Install two groups of support bases for each group of battery packs as follows: Place support
bases on the floor, determine the distance (greater than or equal to 280 mm) between the two
groups of support bases, place battery packs on the support bases in sequence, and secure them.
Do not touch uninsulated battery terminals.
Otherwise, electric shocks may occur.
8
M6×16(6PCS)
3N•m