WIRING
HNET TO NEXT
Siemens Industry, Inc.
Building Technologies Division
Alternate Language Custom Message: This message associated with the
SSD module is in an alternate language.
Display Type: Determines the mode configuration of the SSD. The SSD can
only be set to Display-Only.
Sounder Enabled: If selected, the sounder activates on event receptions;
otherwise, the sounder is disabled.
Display Alarms: If selected, alarm events are displayed on the SSD; other-
wise, alarm events are filtered.
Display Security Events: If selected, security events are displayed on the
SSD; otherwise, security events are filtered.
Display Supervisory Events: If selected, supervisory events are displayed on
the SSD; otherwise, supervisory events are filtered.
Display Troubles: If selected, trouble events are displayed on the SSD;
otherwise, trouble events are filtered.
Remove all system power before installation, first battery, then AC. (To power up,
connect the AC first, then the battery.)
Refer to Figure 5 for a typical wiring connection of Model SSD to the FireFinder-XLS/
Desigo Fire Safety Modular/Cerberus PRO Modular System.
ENCLOSURE
PAIR A (STYLE 4, STYLE 7)
SSD
24VDC (POWER LIMITED)
Figure 5
Typical SSD Connection to the FireFinder-XLS/Desigo Fire Safety Modular/Cerberus
PRO Modular
NIC-C
PAIR B (STYLE 7 ONLY)
FireFinder-XLS/Desigo Fire Safety Modular/
Cerberus PRO Modular ENCLOSURE
6
PMI/PMI-2/
PMI-3 (XLS),
FCM2041-U2
(Desigo Fire Safety
Modular),
FCM2041-U3
(Cerberus
PRO Modular)
CPC
PSC-12
P/N 315-034170-13