Lc - Foundation Dimensions - Sanyo Carrier 16LJ Series Installation Instructions Manual

Single-effect hot water-fired absorption chillers
Table of Contents

Advertisement

4.3 - exhibit LC
4.3.1 - Foundation dimensions, mm
Fig. 15 - 16LJ-11 to 16LJ-42
AA
BB
A
Fig. 16 - Details of weld
Nut
Weld
NOTES
1.
The machine base has a ø50-mm hole for the anchor bolt.
2.
The anchor bolt should be fixed as shown in the detail
drawing. The washer should be welded to the base (see
Fig. 16).
3.
There should be a drain channel around the foundation.
16LJ
Weight, kg
AA + BB
AA
11
4000
2000
12
4200
2100
13
5200
2600
14
5500
2750
21
6700
3350
22
7100
3550
23
8200
4100
24
8700
4350
31
10600
5300
32
11100
5550
41
12900
6450
42
13400
6700
51
18200
9100
52
19700
9850
53
21100
10550
D
C
F
E
G
K
J
150
Washer
80
base
150 mm min.
table 2 - Dimensional data
Dimensions, mm
BB
A
B
2000
1896
--
2100
1896
--
2600
2916
--
2750
2916
--
3350
2866
--
3550
2866
--
4100
3886
--
4350
3886
--
5300
3836
--
5550
3836
--
6450
3836
--
6700
3836
--
9100
3706
130
9850
4248
130
10550
4746
130
Fig. 17 - 16LJ-51 to 16LJ-53
AA
B
4.
The floor surface should be made waterproof to facilitate
maintenance work.
5.
The surface of the foundation should be made flat
(levelling tolerance is 1 mm for 1000 mm).
6.
Anchor bolts and nuts are to be supplied by the customer.
C
D
e
185
360
800
185
360
800
185
360
800
185
360
800
200
400
1000
200
400
1000
200
400
1000
200
400
1000
225
450
1100
225
450
1100
225
450
1150
225
450
1150
190
510
1600
190
510
1600
190
510
1600
F
BB
E
G
K
A
F
G
J
150
1100
160
150
1100
160
150
1100
160
150
1100
160
150
1300
200
150
1300
200
150
1300
200
150
1300
200
150
1400
250
150
1400
250
150
1450
250
150
1450
250
180
1960
250
180
1960
250
180
1960
250
D
J
C
B
150
K
900
900
900
900
1100
1100
1100
1100
1200
1200
1250
1250
1700
1700
1700
2

Advertisement