Open User Communication; Connection Ids For The Profinet Instructions - Siemens SIMATIC S7 System Manual

Hide thumbs Also See for SIMATIC S7:
Table of Contents

Advertisement

103BCommunication
10.2 PROFINET
10.2.2

Open user communication

10.2.2.1

Connection IDs for the PROFINET instructions

When you insert the TSEND_C, TRCV_C or TCON PROFINET instructions into your user
program, STEP 7 creates an instance DB to configure the communications channel (or
connection) between the devices (Page 118). Use the "Properties" of the instruction to
configure the parameters for the connection. Among the parameters is the connection ID for
that connection.
● The connection ID must be unique for the CPU. Each connection that you create must
● Both the local CPU and the partner CPU can use the same connection ID number for the
● You can use any number for the connection ID of the CPU. However, configuring the
Note
Each TSEND_C, TRCV_C or TCON instruction in your user program creates a new
connection. It is important to use the correct connection ID for each connection.
396
have a different DB and connection ID.
same connection, but the connection ID numbers are not required to match. The
connection ID number is relevant only for the PROFINET instructions within the user
program of the individual CPU.
connection IDs sequentially from "1" provides an easy method for tracking the number of
connections in use for a specific CPU.
S7-1200 Programmable controller
System Manual, 11/2011, A5E02486680-05