Appendix
Menus
For installers
Menu
212
Aquarea air-to-water heat pumps - Planning and installation manual - 01/2018
Standard setting
Setting options /Display
Switching behaviour Parallel extended
Heating
Selection of the tank
• "Heating" stands for buffer tank and "Hot
water" stands for domestic hot water tank.
Switching behaviour Parallel extended Heating Yes
• The buffer tank is only activated after "Yes"
has been selected.
Temperature threshold
value for switching on
-8 °C
the bivalent heating
source.
Delayed switching on
for the bivalent heating
0:30
source.
(in hours and minutes)
Temperature threshold
value for switching off
-2 °C
the bivalent heating
source.
Delayed switching off
for the bivalent heating
0:30
source.
(in hours and minutes)
Switching behaviour Parallel extended Hot water Yes
• The domestic hot water tank is only activated
after "Yes" has been selected.
Delayed switching on
for the bivalent heating
0:30
source.
(in hours and minutes)
Menu
5.11
Outdoor On/Off switch
5.12
Solar connection
• In order to be able to operate
this function, the optional
supplementary PCB must be
installed and activated.
• If "Connection of optional
PCB" is not selected, the
function will not be shown in
the display.
Aquarea air-to-water heat pumps - Planning and installation manual - 01/2018
Standard setting
Setting options /Display
No
No
Yes
Selection of the buffer
tank or of the hot
Buffer tank
water tank for the solar
connection
Yes According to the hot water tank selected
Switch on temperature
10 °C
difference
Yes According to the hot water tank selected
T-switch-on temperature
Setting the switch-off
5 °C
temperature difference
Yes According to the hot water tank selected
T-switch-on temperature
T-switch-off temperature
Frost protection
5 °C
temperature
Yes According to the hot water tank selected
T-switch-on temperature
T-switch-off temperature According to setting of the frost protection
temperature
Temperature upper
80 °C
limit
Appendix
213