Mitsubishi Electric MELSEC iQ-R Series Programming Manual page 53

Motion module instructions, standard functions/ function blocks
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Ex.
When timers Time_0 to Time_2 are programmed in order of measurement
[Label definitions]
Label name
Time_0
Time_1
Time_2
Flag_Label
ENO_Label
[Program]
ENO_Label := OUT_T(Flag_Label,Time_0,1);
ENO_Label := OUT_T(Time_0.S,Time_1,1);
ENO_Label := OUT_T(Time_1.S,Time_2,1);
Operation error
There is no operation error.
Data type
Timer
Timer
Timer
Bit
Bit
(1) Timer Time_0 starts measurement when Flag_Label turns on.
(2) When the contact of timer Time_0 turns on, the contacts of timers Time_1
and Time_2 also turn on.
Class
VAR
VAR
VAR
VAR
VAR
5 SEQUENCE INSTRUCTIONS