Check of Density Limit

 U-100PZH2E5
The refrigerant (R32), which is used in the air conditioner, is a flammable refrigerant. So the
requirements for installation space of appliance are determined according to the refrigerant
charge amount [mc] used in the appliance.
The minimum indoor floor space compared with the amount of refrigerant is roughly as follows,
in case it is installed in a living area:
PAW-VP200LDHW, PAW-VP500LDHW must be calculated as wall mounted.
[m
]: the refrigerant charge amount (Total of refrigerant at shipment and refrigerant charge
c
amount in the field)
[m
]: maximum refrigerant charge amount
max
(m
max
PAW-VP•LDHW - Technical Manual – 2019-11
35.0
32.5
30.0
27.5
25.0
22.5
20.0
17.5
15.0
12.5
10.0
7.5
5.0
2.5
0.0
0.03
0.5
1.0
1.22
U-100PZH2E5
U-100PZH2E8
3,50 kg
Can be installed
Can be installed
1.5
2.0
2.53
3.0
[mc]: the refrigerant
[m
] : the refrigerant
c
charge amount (kg)
charge amount (kg)
Safety Instructions
* U-100PZH2E5, U-100PZH2E8
* U-100PZ2E5, U-100PZ2E8
Can not be installed
Can not be installed
Can not be installed
Can not be installed
3.5
4.0
4.5
3.50
3.88
5.0
17