Detailed Settings For Indoor/Outdoor Unit Rtc5B/Rtc2/4 - Panasonic PAW-VP1000LDHW Technical Manual

Air-to-water heat pump systems, domestic hot water system for r410a and r32 use
Hide thumbs Also See for PAW-VP1000LDHW:
Table of Contents

Advertisement

How to make Settings
9.2
9
104

Detailed settings for indoor/outdoor unit RTC5B/RTC2/4

The new value must be set during the commissioning
Tank controller CZ-RTC5B detailed settings
Parameter
Default value
10
0031
11
0012
16
0015
2C
0000
Outdoor unit detailed settings by RTC2/4
Parameter
Default value
20
-015
21
150
4E
000
4F
000
42
-002
A5
000
Tank controller CZ-RTC5B detailed settings
Parameter
Default value
10
0031
11
0012
16
0015
2C
0000
Outdoor unit detailed settings by RTC2/4
Parameter
Default value
20
-015
21
10
4E
000
4F
000
42
-002
A5
000
Tank controller CZ-RTC5B detailed settings
Parameter
Default value
10
0031
11
0012
16
0015
2C
0000
Outdoor unit detailed settings by RTC2/4
Parameter
Default value
20
-015
21
180
4E
000
4F
000
42
-002
A5
000
U-100PZH2E5/VP200LDHW
Explanation
New value to set
0031
Water unit
0012
Indoor capacity type 100
0000
No fan
0006
No expansion valve
Explanation
New value to set
-035
Th. Off differential change from 1.5 k to 3.5 k
600
Th. Off judging time in sec.
+005
Condensing temperature lower limit
+005
Condensing temperature upper limit
000
Condensing temp. offset from -2 k to 0 k
030
Frost adherence temp. change from -2 °C to -4 °C
U-100PZH2E5/VP500LDHW
Explanation
New value to set
0031
Water unit
0015
Indoor capacity type 100
0000
No fan
0006
No expansion valve
Explanation
New value to set
-035
Th. Off differential change from 1.5 k to 3.5 k
600
Th. Off judging time in sec.
+005
Condensing temperature lower limit
+005
Condensing temperature upper limit
000
Condensing temp. offset from -2 k to 0 k
030
Frost adherence temp. change from -2 °C to -4 °C
U-250PZH2E8/PAW-VP750LDHW
Explanation
New value to set
0031
Water unit
0023
Indoor capacity type 250
0000
No fan
0006
No expansion valve
Explanation
New value to set
-035
Th. Off differential change from 1.5 k to 3.5 k
600
Th. Off judging time in sec.
+005
Condensing temperature lower limit
+005
Condensing temperature upper limit
000
Condensing temp. offset from -2 k to 0 k
030
Frost adherence temp. change from -2 °C to -4 °C
Check and adjust
Check and adjust
Check and adjust
Check and adjust
Check and adjust
Check and adjust
PAW-VP•LDHW - Technical Manual – 2019-11