GE 1200 Series Interconnection And Wiring Manual page 33

Fire panels, repeaters, and emulators
Table of Contents

Advertisement

Current requirements
Table 6: Normal operation (battery powered)
Current required by system
Loop current
- 2 loops
- 127 devices/loop @ 340 µA/device (DP951)
Auxiliary current
Total normal current
Table 7: Alarm operation (battery powered)
Normal current (as Table 6)
Extra loop current (20 x LED @ 4 mA)
Sounders (sounder board: outputs 1-4)
Total alarm current
Table 8: Normal operation (mains powered)
Mains load (maximum)
Total output current (27.6 V)
Battery capacity I
= 0 (72H standby)
AUX
Battery capacity (maximum)
Required battery charging current (maximum
battery capacity)
Current required by system (I
Available auxiliary current
*I
calculated at 252 x 900 series ionisation detectors (FP2416/64) 1008 x 900 series ionisation detectors (FP2864/255)
SYS
FP12XX
200 mA (max)
86 mA
0 mA
286 mA
FP12XX
286 mA (max)
80 mA
200 mA
566 mA
FP2416/2464 & FP2432/24128
200 VA
4 A
36 AH
68 AH
3.05 A
)*
0.5 A
SYS
0.45 A
1200-2000 Series Fire Panels, Repeaters, and Emulators
Interconnection and Wiring Guide
FR1200/FR2000
200 mA (max)
0 mA
0 mA
200 mA
FR1200/FR2000
200 mA (max)
0 mA
0 mA
200 mA
FP2864/28255 &
FP2864N/28255N
200 VA
4 A
58 AH
68 AH
3.05 A
0.8 A
0.15 A
FP1216EN / FP1264 /
FP12xxN
200 mA (max)
86 mA
0 mA
286 mA
FP1216EN / FP1264 /
FP12xxN
286 mA (max)
80 mA
200 mA
566 mA
33