2 Parameters
2.2 List of parameters
r4052[0...1]
CO: TM31 analog inputs current input voltage/current / TM31 AI U/I_inp
TM31
Can be changed: -
Data type: FloatingPoint32
P-Group: Terminals
Not for motor type: -
Min
-
Description:
Displays the actual input voltage in V when set as voltage input.
Displays the actual input current in mA when set as current input and with the load resistor switched in.
Index:
[0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
Dependency:
The type of analog input AI x (voltage or current input) is set using p4056.
Refer to: p4056
Note:
AI: Analog Input
p4053[0...1]
TM31 analog inputs smoothing time constant / TM31 AI T_smooth
TM31
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Terminals
Not for motor type: -
Min
0.0 [ms]
Description:
Sets the smoothing time constant of the 1st-order low pass filter for the analog inputs of Terminal Module 31 (TM31).
Index:
[0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
Note:
AI: Analog Input
r4055[0...1]
CO: TM31 analog inputs actual value in percent / TM31 AI value in %
TM31
Can be changed: -
Data type: FloatingPoint32
P-Group: Terminals
Not for motor type: -
Min
- [%]
Description:
Displays the currently referred input value of the analog inputs of Terminal Module 31 (TM31).
When interconnected, the signals are referred to the reference quantities p200x and p205x.
Index:
[0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
Note:
AI: Analog Input
p4056[0...1]
TM31 analog inputs type / TM31 AI type
TM31
Can be changed: U, T
Data type: Integer16
P-Group: Terminals
Not for motor type: -
Min
0
Description:
Sets the type of analog inputs of Terminal Module 31 (TM31).
p4056[x] = 0, 4 correspond to a voltage input (r4052, p4057, p4059 are displayed in V).
p4056[x] = 2, 3, 5 correspond to a current input (r4052, p4057, p4059 are displayed in mA).
In addition, the associated switch S5 must be appropriately set.
224
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
1000.0 [ms]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: PERCENT
Max
- [%]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
5
List Manual (LH8), 02/2015, 6RX1800-0ED76
Access level: 1
Func. diagram: 9566, 9568
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 1
Func. diagram: 9566, 9568
Unit selection: -
Expert list: 1
Factory setting
0.0 [ms]
Access level: 1
Func. diagram: 9549, 9566,
9568
Unit selection: -
Expert list: 1
Factory setting
- [%]
Access level: 1
Func. diagram: 9566, 9568
Unit selection: -
Expert list: 1
Factory setting
4